Test voltages
500, 1000, 2500, 5000 V directly, one button selectable.
500 V to 5 kV in 100 V increments. DC, negative.
Maximum resistance reading
5 TΩ @ 5 kV.
Short circuit current
1.5 ± 0.5 mA.
Test voltages accuracy
± 3 % of nominal test voltages on R ≥ 10 GΩ.
Insulation tester basic accuracy
± 5 % of reading from 1 MΩ up to 1 TΩ.
± 20 % of reading from 1 TΩ up to 5 TΩ.
Advanced features
Automated polarization index calculation.
Automated dielectric absorption ratio calculation.
Step voltage test.
Programmable pass / fail test.
Built-in printer
Prints elapsed time, actual voltage and resistance measured each 15 seconds.
Built-in memory
Stores up to 4000 measured values.
Interface
USB.
Built-in chronometer
Shows elapsed time in mm:ss format. Count starts automatically for each measurement.
Real time clock and calendar
Allows a reliable identification for each test.
T-Logger software
Friendly, easy to use software. Tests are represented in graphical and tabular views. With automatic report generator, including the operator's commentaries.
Environmental protection
IP54 (with closed lid).
Safety class
In accordance with IEC 61010-1.
E.M.C.
In accordance with IEC 61326-1.
Electrostatic immunity
In accordance with IEC 61000-4-2.
Electromagnetic irradiation immunity
In accordance with IEC 61000-4-3.
Power supply
Internal rechargeable LFP 12 V - 3000 mAh battery.
Battery charger
12 V - 2 A.
Operating temperature range
23 °F to 122 °F (-5 °C to 50 °C).
Storage temperature range
-13 °F to 158 °F (-25 °C to 70 °C).
Humidity range
95 % RH (non condensing).
Equipment weight
Approx. 7.94 lb (3.6 kg).
Dimensions
10.78" x 9.84" x 4.88" (274 x 250 x 124 mm).
Included accessories
2 Measuring test leads.
1 GUARD test lead.
1 AC Adapter.
1 T-Logger software (CD-ROM).
1 User guide.
1 Protective bag.
1 USB cable.