NP40 Portable Power Quality Analyzer

Overview

NP40 power quality analyzer is the professional portable device to measure and analyze the power system quality, supply the harmonics analysis and power quality data analysis, also provide big memory for the data storage, which is used to make the long term logger measuring to power system.

The PC software can simply upload the data to PC for full analysis.

Download our data sheet

user_manual_download

  • 5,6" TFT color screen, 320 x 240 pixel
  • Waveform real-time display (4 voltages/4 currents)
  • Half cycle RMS measurement (voltage and current)
  • Measurement of TRMS currents up tp 3000 A (with standard probes mode)
  • Measurement in 1-phase and 3-phase systems (3 - and 4-wire).
  • Measurement of voltage, current, harmonics, power, energy, inrush current, fl icker and other.
  • Graphical presentation of data in a waveform and vector diagram
  • Record of events: dips, swells, overvoltages
  • Power quality according to EN-50160 standard or user-defined limit
  • Internal memory for data logging needs (continuous registration from 2 hours to 7 days)
  • The registration frequency from 1 second up to 60 minutes
  • Built-in 8G memory card
  • Ethernet interface for remote operation of the analyzer
  • USB Host to move archive data and screenshots to an external USB memory
  • Safety standards: EN 61010-1, CAT III 1000V / CAT IV 600V
  • The analyser set: analyzer, fl exible probes mode 3000A (4x), voltage tests leads aligator clips (5x), DC power adapter, CD with software, user’s manual

INPUTS

VOLTAGE INPUTS

Input Channels: 4 (3-phase + neutral)
Max. input voltage: 1000 Vrms
Range of nominal voltage: 50...500V
Max pulse peak voltage: 6kV
Bandwidth: >3kHz
Input impedance: 4MΩ/5pF

CURRENT INPUT

Number of input: 4 (3-phase+ neutral) DC coupling
Type: clamp current sensor with mV output
Input range: 1...3000 Arms with supplied current clamp
Input Impedance: 50 kΩ
Bandwidth: >3kHz

SAMPLING SYSTEM

Resolution: 8 channels 16 bits AD
Sampling rate: 20kS/s for each channel, 8 channels sample synchronously
RMS sampling: 5000 points for 10/12 cycles (according to EN 61000-4-30)
PLL synchronizacja: 4096 points for 10/12 cycles (according to EN 61000-4-7)

TOP UA-62970234-2 });